Hardware errors
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
62
x signal Determination of the measured data for the actuator has failed.
Conductive plastic element is defective.
The positioner continues to run in emergency mode, but should
be replaced as soon as possible.
The emergency mode on the display is indicated by a blinking
closed-loop operation icon and 4 dashes instead of the position
indication.
Note on the closed-loop operation:
If the measuring system has failed, the positioner is still in a reli
-
able state. The positioner switches to emergency mode where the
position cannot be accurately controlled anymore. However, the
positioner continues operation according to its set point signal so
that the process remains in a safe state.
Status classification
[Maintenance demanded]
Recommended action
Return the positioner to SAMSON AG for repair.
64
i/p converter The circuit of the i/p converter has been interrupted.
Status classification
Maintenance alarm (cannot be classified)
Recommended action
Cannot be remedied.
Return the positioner to SAMSON AG for repair.
EB 8384-4 EN 91
Code list