Code
no.
Parameter – Display, values
[default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
5*
Nominal range
mm or angle °
ESC
For initialization using NOM or SUb, the nominal travel/angle of
rotation of the valve must be entered.
The permissible adjustment range depends on the pin position
according to the table for Code 4.
Code 5 is generally locked until Code 4 is set to
No, i.e. after a
pin position has been entered, Code 5 can be configured.
After initialization has been successfully completed, the maxi
-
mum nominal travel/angle reached on initialization is displayed.
6*
Init mode
[MAX]
NOM
MAN
SUb
ZP
ESC
Select the initialization mode
MAX: Travel/angle of the closure member from the CLOSED
position to the opposite stop in the actuator.
NOM: Travel/angle of the closure member measured from the
CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUb: Substitute calibration (without initialization)
7*
w/x
[ää] increasing/increasing
äæ increasing/decreasing
ESC
Direction of action of the set point w in relation to the travel/an-
gle of rotation x
Automatic adaptation:
AIR TO OPEN:
On completing initialization, the direction of action remains in-
creasing/increasing (ää), a globe valve opens as the mA signal
increases.
AIR TO CLOSE:
On completing initialization, the direction of action changes to
increasing/decreasing (äæ), a globe valve closes as the mA sig
-
nal increases.
8*
Travel/angle range start
(lower x-range value)
0.0 to 80.0 [0.0] % of the
nominal range
ESC
Note: Specified in mm or
angle ° provided Code 4 is
set
Lower range value for the travel/angle of rotation in the nominal
or operating range.
The operating range is the actual travel/angle of the control
valve and is limited by the lower x-range value (Code 8) and the
upper x-range value (Code 9).
Usually, the operating range and the nominal range are identi
-
cal. The nominal range can be limited to the operating range by
the lower and upper x-range values.
Value is displayed or must be entered.
The characteristic is adapted. See also the example in Code 9!
EB 8384-4 EN 81
Code list