Select the initialization mode:
Initialization mode
Default
MAX
Turn
→
Code 6
Press , Code 6 blinks
Turn
→
SUb
Press to confirm the SUb as the initializa
-
tion mode.
Enter the direction of action:
Default ää
Turn
→
Code 7
Press , Code 7 blinks
Turn
→
Direction of action (ää or äæ)
Press .
Deactivate travel limit:
Default 100.0
Turn
→
Code 11
Press , Code 11 blinks
Turn
→
No
Press .
Change pressure limit and control parame
-
ters:
Note: Do not change the pressure limit
(Code 16). Only change the control param
-
eters K
P
(Code 17) and T
V
(Code 18) if the
settings of the the replaced positioner are
known.
Pressure limit
Default
No
KP
Default
7
TV
Default
2
Turn
→
Code 16/17/18
Press , Code 16/17/18 blinks
Turn to set the control parameter se
-
lected.
Press to confirm the setting.