Actuator stem retracts FE (AIR TO CLOSE)
Fail-open (for globe and angle valves):
For tight-closing valves, the maximum signal
pressure pst
max
is roughly estimated as fol
-
lows:
pst
max
= F +
d p
A
2
4
⋅ ⋅
⋅
π ∆
[bar]
d = Seat diameter [cm]
∆
p = Differential pressure across the valve
[bar]
A = Actuator diaphragm area [cm²]
If there are no specifications, calculate as
follows:
Required supply pressure =
Upper bench range value + 1 bar.
5.1.3 Signal pressure (output)
The signal pressure at the output (Out-
put 38) of the positioner can be limited to
1.4, 2.4 or 3.7 bar in Code 16.
The limitation is not activated [OFF] by de
-
fault.
5.2 Electrical connections
DANGER!
Risk of electric shock and/or
the formation of an explosive
atmosphere!
–
For electrical installation, observe the rel
-
evant electrotechnical regulations and
the accident prevention regulations that
apply in the country of use.
–
The following regulations apply to
mounting and installation in hazardous
areas: EN 60079-14: 2008 Explosive
atmospheres – Part 14: Electrical instal
-
lations design, selection and erection (or
VDE 0165 Part 1).
NOTICE
– Adhere to the terminal assignment!
Switching the assignment of the electrical
terminals may cause the explosion pro-
tection to become ineffective!
–
Do not loosen enameled screws in or on
the housing.
–
The maximum permissible values speci
-
fied in the national EC type examination
certificates apply when interconnecting
intrinsically safe electrical equipment (U
i
or U
o
; I
i
or I
o
; P
i
or P
o
; C
i
or C
o
, and L
i
or
L
o
).
Selecting cables and wires:
Observe Clause 12 of EN 60079-14: 2008
when installing intrinsically safe circuits. The
Subclause 12.2.2.7 applies when running
multi-core cables containing more than one
intrinsically safe circuit.
48 EB 8384-4 EN
Connections