Initialization errors
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
50
x > range The value supplied by the measuring signal is either too high or
too low, the measuring sensor is close to its mechanical limit.
• Pin positioned incorrectly.
• Bracket slipped in case of NAMUR attachment or positioner is
not central.
• Follower plate incorrectly attached.
Status classification
[Maintenance required]
Recommended action
Check attachment and pin position, set operating mode from
SAFE to MAN and re-initialize the positioner.
51
∆
x < range The measuring span of the sensor is too low.
• Pin positioned incorrectly.
• Wrong lever.
A rotational angle smaller than 16° at the positioner shaft creates
just an alarm. An angle below 9° leads to the initialization being
canceled.
Status classification
[Maintenance required]
Recommended action
Check attachment and re-initialize the positioner.
52
Attachment • Positioner attachment incorrect.
• Nominal travel/angle (Code 5) could not be achieved during
initialization under NOM (no tolerance downwards
permissible).
• Mechanical or pneumatic fault, e.g. wrong lever selected or
supply pressure too low to move to the required position.
Status classification
[Maintenance required]
Recommended action
Check attachment and supply pressure. Re-initialize the
positioner.
Under certain circumstances, it may be possible to check the
maximum travel/angle by entering the actual pin position and
then performing an initialization under MAX.
After initialization has been completed, the Code 5 indicates the
maximum achieved travel or angle.
88 EB 8384-4 EN
Code list