Readings on display
Icons appear on the display that are as
-
signed to parameters, codes and functions.
Operating modes:
4
Manual mode (MAN), section 8.2.1
The positioner follows the manual set
point (Code 1) and not the set point pro
-
vided by the process control system.
blinks: The positioner has not yet
been initialized. Operation only possible
over manual set point (Code 1).
4
Automatic mode (AUTO), sec
-
tion 8.2.1
The positioner is in closed-loop operation
and follows the set point provided by the
process control system.
4
SAFE, section 8.2.2
The positioner vents the output. The valve
is moved to the mechanical fail-safe po-
sition.
Bar graph:
In manual and automatic modes, the
bars indicate the system deviation that de
-
pends on the sign (+/–) and the value. One
bar element appears per 1 % system devia
-
tion.
If the device has not yet been initialized, the
icon blinks on the display and the lever
position in degrees in relation to the longitu
-
dinal axis is indicated. One bar element cor
-
responds to approximately a 5° angle of ro
-
tation.
If the fifth bar element blinks (reading
> 30°), the permissible angle of rotation has
been exceeded. Lever and pin position must
be checked.
Status alarms
4
: Maintenance alarm
4
: Maintenance required/demanded
These icons indicate that an error has oc
-
curred. A classified status can be as
-
signed to each error. Classifications in
-
clude “No message”, “Maintenance re
-
quired”, “Maintenance demanded” and
“Maintenance alarm“ (see section 8.3).
Configuration enabled
This indicates that the codes marked with an
asterisk (*) in the code list (section 14) are
enabled for configuration (see section 8.1).
54 EB 8384-4 EN