Note: If the positioner shows a tendency to
oscillate in automatic operating mode, the
parameters K
P
and T
V
must be slightly cor
-
rected. Proceed as follows:
–
Set T
V
to 4 (Code 18).
–
If the positioner still oscillates, the gain
K
P
(Code 17) must be decreased until the
positioner shows a stable behavior.
Zero point calibration
Finally, if process operations allow it, the
zero point must be adjusted according to
section 7.7.
7.7 Zero calibration
In case of discrepancies with the closing po-
sition of the valve, e.g. with soft-sealed
plugs, it may become necessary to
recalibrate the zero point.
NOTICE
The valve briefly moves from the current
travel/angle of rotation position to the
closed position.
Note: The positioner must be connected to
the supply air to perform the zero calibra
-
tion.
Enable configuration:
Turn
→
Code 3
Press , Code 3 blinks
Turn
→
ON
Press , display
Perform zero calibration:
Initialization mode
Default
MAX
Turn
→
Code 6
Press , Code 6 blinks
Turn
→
ZP
Press .
4
Press INIT key
Zero calibration starts.The positioner moves
the valve to the CLOSED position and read
-
justs the internal electrical zero point.
7.8 Reset to default values
This function resets all parameters to the fac-
tory default values (see code list in sec-
tion 14).
Enable configuration:
Turn
→
Code 3, display No
Press , Code 3 blinks
Turn
→
ON
Press , display
Reset start-up parameters:
Reset
Default
No
Turn
→
Code 36, display ••–••–
68 EB 8384-4 EN
Start-up – Settings