Reading direction for left
attachment of pneumatic
connections
If the displayed data appear upside down,
proceed as follows:
Turn
→
Code
2
Press
→
Code 2 blinks.
Turn
→
Required direction
Press to confirm reading direction.
7.4 Limiting the signal pressure
If the maximum actuator force may cause
damage to the valve, the signal pressure
must be limited.
Enable configuration at the positioner before
activating the pressure limit function:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Configuration enabled
Default:
No
Turn
→
Code 3, display: No
Press
→
Code 3 blinks.
Turn
→
YES
Press
→
display
Limiting the signal pressure:
Pressure limit
Default:
No
Turn
→
Code 16
Press
→
Code 16 blinks.
Turn until the required pressure limit
(1.4/2.4/3.7 bar) appears.
Press to confirm the pressure limit set
-
ting.
7.5 Checking the operating
range of the positioner
To check the mechanical attachment and the
proper functioning, the valve should be
moved through the operating range of the
positioner in the manual operating mode
with the manual set point.
Selecting manual operating mode:
Operating mode
Default
MAN
Turn
→
Code 0
Press
→
Code 0 blinks.
Turn
→
MAN
Press . The positioner changes to the
manual operating mode.
58 EB 8384-4 EN
Start-up – Settings