The time required for an initialization pro
-
cess depends on the transit time of the actu
-
ator and take several minutes. After a suc
-
cessful initialization, the positioner runs in
closed-loop operation indicated by .
A malfunctioning leads to the process being
canceled. The initialization error appears on
the display according to how it has been
classified by the condensed state. See sec
-
tion 8.3.
Note: When Code 48 - h0 = YES, the diag
-
nostics automatically start to plot the refer
-
ence graphs (drive signal steady-state d1
and hysteresis d2) after initialization has
been completed.
tESt d1 or tESt d2 appear on the display in
an alternating sequence.
An error during the plotting of the reference
graphs is indicated on the display over
Code 48 - h1 and Code 81.
The positioner still works properly, even
though the reference graph plotting has not
been completed successfully.
Valve closed position AIR TO CLOSE
If the slide switch is set to AIR TO CLOSE,
the positioner automatically switches to the
direction of action increasing/decreasing
(äæ) on successful completion of initializa
-
tion.
This results in the following assignment be
-
tween set point and valve position:
Valve closed
position
Direction of
action
Set point
Valve
Closed at Open at
AIR TO OPEN ää 0 % 100 %
AIR TO CLOSE äæ 100 % 0 %
The tight-closing function is activated.
NOTICE
Set Code 15 (final position w>) to 99 % for
three-way valves.
Canceling an initalization process
The initialization procedure can be canceled
while running by pressing the rotary
pushbutton ( ).
StOP appears three sec
-
onds long and the positioner then changes
to the fail-safe position (SAFE).
Exit the fail-safe position again over Code 0
(see section 8.2.2).
7.6.1 MAX – Initialization based
on maximum range
The positioner determines travel/angle of
rotation of the closing member from the
CLOSED position to the opposite side and
adopts this travel/angle of rotation as the
operating range from 0 to 100 %.
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default No
EB 8384-4 EN 61
Start-up – Settings