Vista de página 66
Enter closing direction and blocking posi
-
tion:
Closing direction
Direction of rotation caus
-
ing the valve to move to the
CLOSED position (view
onto positioner display)
Default: CCL (counterclock
-
wise)
Blocking position
Default: 0
Turn
Code 34
Press , Code 34 blinks
Turn
Closing direction (CCL counter-
clockwise/CL clockwise)
Press .
Turn
Code
35
Press , Code 35 blinks
Turn
Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Press to confirm the setting.
Set the valve closed position:
4
Set switch for valve closed position
AIR TO OPEN or AIR TO CLOSE as de
-
scribed in section 7.1 on page 56.
4
Set volume restriction as described in
section 7.2 on page 57.
Start initialization:
4
Press INIT key.
The positioner switches to MAN mode.
The blocking position is indicated.
Note: As initialization has not been carried
out completely, the error code 76 (no emer
-
gency mode) and possibly also error code
57 (control loop) may appear on the dis
-
play.
These alarms do not influence the
positioner’s readiness for operation.
Cancel the blocking position and change to
automatic operating mode
For the positioner to follow its set point
again, the blocking position must be can-
celed and the positioner must be set to
automatic operating mode as follows:
Turn
Code 1
Press , Code 1 and blink
Turn in order to move the valve slightly
past the blocking position.
Press to cancel mechanical blocking.
Turn
Code
0
Press , Code 0 blinks.
Turn
AUtO
Press . The positioner switches to auto
-
matic operating mode. The current valve po
-
sition is indicated in %.