4.3 Attachment according to
VDI/VDE 3847
Type 3730-4xxxxxxxx0x0060xx and
Type 3730-4xxxxxxxx0x0070xx Positioners
with air purging of the actuator's spring
chamber can be attached according to
VDI/VDE 3847.
Type 3730-4xxxxxxxx0x0000xx Positioner
without air purging of the actuator's spring
chamber can be attached according to
VDI/VDE 3847.
This type of attachment allows the
positioners to be replaced quickly while the
process is running by blocking the air in the
actuator.
The signal pressure can be blocked in the
actuator by unscrewing the red retaining
screw (20) and then turning the air blocker
(19) on the bottom of the adapter block.
Attachment to Type 3277 Actuator (see
Fig. 7)
Refer to Table 4 on page 44 for the required
mounting parts as well as the accessories.
Mount the positioner on the yoke as shown
in Fig. 7. The signal pressure is routed to the
actuator over the connecting plate (12), for
actuators with fail-safe action "actuator stem
extends" internally through a bore in the
valve yoke and for "actuator stem retracts"
through external piping.
Only the Y1 port is required for positioner
attachment. The Y2 port can be used for air
purging of the spring chamber.
1. Place follower clamp (3) on the actuator
stem, align and screw tight so that the
mounting screw is located in the groove
of the actuator stem.
2. Place the adapter bracket (6) on the
positioner and mount using the screws
(6.1). Make sure that the seals are cor
-
rectly seated. For positioners with air
purging, remove the stopper (5) before
mounting the positioner.
For positioners without air purging, re
-
place the screw plug (4) with a vent plug.
3. For actuators with 355/700/750 cm²,
remove the follower pin (2) at lever M
(1) on the back of the positioner from
pin position 35, reposition it in the bore
for pin position 50 and screw tight.
For actuators 175, 240 and 350 cm²
with 15 mm travel, the follower pin (2)
remains in pin position 35.
4. Insert formed seal (6.2) in the groove of
the adapter bracket.
5. Insert the formed seal (17.1) into the
turnboard (17) and mount the turnboard
to the adapter block (13) using the
screws (17.2).
6. Mount the blank plate (18) to the
turnboard (17) using the screws (18.1)
Make sure that the seals are correctly
seated.
Note: A solenoid valve can also be mounted
in place of the blank plate (18). The orienta
-
tion of the turnboard (17) determine the
mounting position of the solenoid valve. Al
-
ternatively, a restrictor plate can be mounted
(see AB 11 EN).