Parameter – Display, values
[default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
42
Auto-w/manual-w info
0.0 to 100.0 % of the span
Read only,
Auto mode: indicates the supplied automatic set point
Man mode: indicates the supplied manual set point
43
Firmware info control Read only,
indicates the positioner type and current firmware version in
alternating sequence.
44
y info
[0] to 100 %
0P, MAX, – – –
Read only.
Indicates the control signal y in % based on the travel range de
-
termined on initialization
MAX: The positioner builds up its maximum output pressure, see
description in Code 14 and 15.
0P: The positioner vents completely, see description in Code 14
and 15.
– – –: The positioner is not initialized.
45
Solenoid valve info
YES, HIGH/LOW, No
Read only,
indicates whether a solenoid valve is installed or not.
If a voltage supply is connected at the terminals of the installed
solenoid valve,
YES and HIGH appear on the display in alternat-
ing sequence. If a voltage supply is not connected (actuator
vented, fail-safe position indicated on the display by the S icon),
YES and LOW appear on the display in alternating sequence.
46*
Bus address
ESC
Select bus address
47*
Write protection PA
YES, [No], ESC
When the write protection function is activated, device data can
only be read, but not overwritten over PA communication.
48*
49*
Diagnostics (refer to EB 8389 EN on EXPERTplus valve diagnostics)
86 EB 8384-4 EN