In particular, the radial thickness of the con
-
ductor insulation for common insulation ma
-
terials, such as polyethylene, must have a
minimum radial thickness of 0.2 mm.
The diameter of an individual wire in a
fine-stranded conductor must not be smaller
than 0.1 mm. Protect the conductor ends
against splicing, e.g. by using wire-end fer
-
rules.
When two separate cables are used for con
-
nection, an additional cable gland can be
installed.
Seal cable entries left unused with plugs.
Devices used at ambient temperatures be
-
low –20 °C must be fitted with metal cable
glands.
Equipment for use in zone 2/zone 22
In equipment operated with type of protec-
tion Ex nA II (non-sparking equipment) ac-
cording to EN 60079-15: 2003, circuits
may be connected, interrupted or switched
while energized only during installation,
maintenance or repair.
Equipment connected to energy-limited cir
-
cuits with type of protection Ex nL (en
-
ergy-limited equipment) according to
EN 60079-15: 2003 may be switched un
-
der normal operating conditions.
The maximum permissible values specified
in the Statement of Conformity or its ad
-
denda apply when interconnecting the
equipment with energy-limited circuits in
type of protection Ex nL IIC.
Cable entries
The cable entry with M20 x 1.5 cable gland,
6 to 12 mm clamping range.
There is a second M20 x 1.5 threaded bore
in the housing that can be used for addi
-
tional connection, when required.
The screw terminals are designed for wire
cross-sections of 0.2 to 2.5 mm². Tighten by
at least 0.5 Nm.
Note: The power supply for the positioner
can be supplied either over the connection
to the fieldbus segment or over a DC voltage
source (9 to 32 V) connected to the bus ter
-
minals in the positioner.
You are required to observe the relevant
regulations for use in hazardous areas.
Accessories:
Cable gland M20 x 1.5 Order no.
Black plastic
(6 to 12 mm clamping range) 8808-1011
Blue plastic
(6 to 12 mm clamping range) 8808-1012
Nickel-plated brass
(6 to 12 mm clamping range) 1890-4875
Nickel-plated brass
(10 to 14 mm clamping range) 1922-8395
Stainless steel 1.4305
(8 to 14.5 mm clamping range) 8808-0160
EMC cable gland, nickel-plated
brass
8808-0143
Adapter M20 x 1.5 to ½ NPT
Aluminum, powder paint coated 0310-2149
Stainless steel 1400-7114
EB 8384-4 EN 49