6 Operator controls and
readings
Rotary pushbutton
The rotary pushbutton is located underneath
the front protective cover.
The positioner is operated on site using the
rotary pushbutton:
Turn to select codes and values.
Press to confirm setting.
Slide switch AIR TO OPEN or AIR TO CLOSE
4
AIR TO OPEN applies when the increas
-
ing signal pressure opens the valve
4
AIR TO CLOSE applies when the increas
-
ing signal pressure closes the valve
The signal pressure is the air pressure at the
output of the positioner which is transferred
to the actuator.
For positioners with an attached reversing
amplifier for double-acting rotary actuators
(section 4.6): switch position AIR TO OPEN.
Volume restriction Q
The volume restriction is used to adapt the
air delivery to the actuator size. Two fixed
settings are possible depending on how the
air is routed at the actuator:
4
For actuators smaller than 240 cm² with
a loading pressure connection at the side
(Type 3271-5), set restriction to MIN
SIDE.
4
For a connection at the back (Type
3277-5), set restriction to MIN BACK.
4
For actuators 240 cm² and larger, set to
MAX SIDE for a side connection and to
MAX BACK for a connection at the back.
EB 8384-4 EN 53
Operator controls and readings
AIR TO
OPEN
CLOSE
INIT
CAUTION
VALVE
ACTUATES
MIN SIDE
MAX BACK
MIN BACK
MAX SIDE
Q
%
S
mm
SERIAL
INTERFACE
%
mm
Fig. 23 · Operator controls
Initialization key Cap or rotary switch Metal tag of proximity switch
SSP interface
Switch for
AIR TO OPEN/
AIR TO CLOSE
Volume restriction
Rotary pushbutton