Code
no.
Parameter – Display, values
[default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
23*
Total valve travel
0 to 99 · 10
7
[0]
Exponential reading from 9999 travel
cycles onwards
RES, ESC
Totaled double valve travel.
Can be reset to 0 by
RES.
Note: The total valve travel is saved in a non-volatile memory
after every 1000 double travel.
24*
LV total valve travel
1000 to 99 · 10
7
[1 000 000]
Exponential reading from 9999 travel
cycles onwards
ESC
Limit value of total valve travel. If the limit is exceeded, the fault
symbol and the wrench symbol corresponding with the collective
status appear.
34*
Closing direction
CL Clockwise
[CCL] Counterclockwise
ESC
Turning direction in which the valve is moved to the CLOSED po
-
sition (view onto the rotary switch motion when the positioner
cover is open).
Needs only be entered in initialization mode
SUb (Code 6).
35*
Blocking position
[0] mm/° /%
ESC
Entering the blocking position.
Distance up to the CLOSED position.
Only necessary in initialization mode
SUb.
36*
Reset
[No], Std, diAG, ESC
Std: Resets all parameters to default (factory setting) as well
as the diagnosis data. After a reset, the positioner must
be re-initialized.
diAG: Resets diagnosis data only. Plotted reference graphs and
logs remain unaffected. The positioner does not need to
be re-initialized.
38*
Inductive alarm
[No], YES, ESC
Indicates whether the inductive limit switch option is installed or
not.
39
System deviation e info
–99.9 to 999.9 %
Read only,
indicates the deviation from the position required.
40
Transit time Open info
0 to 240 s [0]
Read only,
minimum opening time determined during initialization.
41
Transit time Closed info
0 to 240 s [0]
Read only,
minimum closing time determined during initialization.
EB 8384-4 EN 85
Code list