7. Mount the blank plate (18) to the
turnboard (17) using the screws (18.1)
Make sure that the seals are correctly
seated.
Note: A solenoid valve can also be mounted
in place of the blank plate (18). The orienta
-
tion of the turnboard (17) determine the
mounting position of the solenoid valve. Al
-
ternatively, a restrictor plate can be mounted
(see AB 11 EN).
8. Mount the adapter block (13) to the
NAMUR connection block using the
screws (13.1).
9. Insert the vent plug (11.1) into the Exh.
connection.
10.Place the positioner on the adapter block
(13) in such a manner that the follower
pin (2) rests on the top of the follower
clamp (3). Adjust the lever (1) corre-
spondingly.
Fasten the positioner to the adapter
block (13) using the two fixing screws
(6.3). Make sure the formed seal (6.2) is
properly seated.
11.For single-acting actuators without air
purging connect the Y1 port of the
adapter block to the signal pressure con
-
nection of the actuator. Seal the Y2 port
with a blanking plug.
For double-acting actuators and actua
-
tors with air purging connect the Y2
port of the adapter block to the signal
pressure connection of the second actua
-
tor chamber or spring chamber of the
actuator.
26 EB 8384-4 EN
Attachment to the control valve – Mounting parts and accessories
Comentários a estes Manuais