Addendum Page 2
Revisions Control No. 1: March.2006 Addendum to EB 8384-5 EN
Intrinsically safe if installed as specified in manufacturer’s installation manual.
CSA- certified for hazardous locations Type 4 Enclosure
Ex ia IIC T6
Class I, Division 1, Groups A, B, C and D; Class II, Division 1, Groups E, F + G; Class III.
Model 3730-43/3730-53
Positioners
11+
12
-
41+
42-
85+
86-
Fieldbus
circuit 1
Limit switch circuit 2
81+ Forced venting function
82
-
circuit 3
Terminal No.
I.S.Ground
CSA-certified
termination with
R = 90 . . .100,
C = 0 . . .2,2µF
CSA-certified
intrinsically safe
apparatus suitable
for FIELDBUS
CSA-certified
intrinsically safe
apparatus suitable
for FIELDBUS
CSA-certified associated
apparatus suitable
for Profibus PA or FOUNDATION FF
FIELDBUS
Binary contact 2
circuit 5
supply barrier
evaluation barrier
CSA
-
certified barrier
Isolating amplifier 1 or 2
channels
CSA- certified
Hazardous
Location
Safe
Location
Installation shall be in accordance with the C.E.C. Part 1
87+ Binary contact 1
88- circuit 4
evaluation barrier
supply barrier
.
External position sensor
(optionally)
Serial in
terface, for connection
to CSA certified intrinsically
safe circuit
Addendum Page 1
Revisions Control No. 1: March.2006 Addendum to EB 8384-5 EN
Installation Manual for apparatus certified by CSA for use in hazardous locations.
Communication is optionally either according to the FOUNDATION
TM
Fieldbus Specification or
according to PROFIBUS PA in compliance FISCO-Concept
The FISCO Concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in
such combination. The criteria for interconnection is that the voltage (V
max
) the current (I
max
) and the power (P
max
) which
intrinsically safe apparatus can receive and remain intrinsically safe, considering faults, must be equal or greater than the voltage
(V
0C
) the current (I
SC
) and the power (P
0
) levels which can be delivered by the associated apparatus, considering faults and
applicable factors. In addition, the maximum unprotected capacitance (C
i
) and inductance (L
i
) of each apparatus (other than the
termination) connected to the fieldbus must be less than or equal to 5 nF and 10 µH respectively.
In each segment only one active device, normally the associated apparatus, is allowed to provide the necessary energy for the
fieldbus system The allowed voltage (V
0C
) of the associated apparatus is limited to the range of
14V DC. to 24V DC. All other equipment connected to the bus cable has to be passive, meaning that they are not allowed to
provide energy to the system, except to a leakage current of 50mA for each connected device. Separately powered equipment
needs a galvanic isolation to assure that the intrinsically safe fieldbus circuit remains passive.
The cable used to interconnect the devices need to have the parameters in the following range:
Loop resistance R‘: 15 ... 150 Ohm/km
Inductance per unit length L‘: 0,4 ... 1 mH/km
Capacitance per unit length C‘: 80 ... 200 nF/km
C‘ = C‘ line/line + 0,5 C‘ line/screen, if both lines are floating or, C‘ = C‘ line/line + C’line/screen, if the screen is
connected to one line
Length of spur cable: 30 m
Length of trunk cable: 1 km
At each end of the trunk cable an approved infallible line termination with the following parameters is suitable:
R = 90 ... 100 Ohm C = 0 ... 2,2 µF
One of the allowed terminations might already be integrated in the associated apparatus.
The number of passive devices connected to the bus segment is not limited due to I.S. reasons. If the above rules are respected,
the inductance and capacitance of the cable will not impair the intrinsic safety of the installation.
Notes:
1. Approved associated apparatus must be installed in accordance with manufacturer instructions
2. Approved associated apparatus must meet the following requirements:
V
oc
Vmax, Isc Imax, Po
Pmax
3. The maximum non-hazardous area voltage must not exceed 250 V.
4. The installation must be in accordance with the Canadian Electrical code Part 1.
5. Each set of wires must be provided with grounded shield. The shield must extend as close to the terminal(s) as possible
and it must be grounded shield at I. S. Barrier ground.
6. Caution: Use only supply wires suitable for 5 °C above surrounding.
7. Warning: Substitution of components may impair intrinsic safety. PE = I. S. Ground
8. The polarity for connecting 11 and 12 is of no importance due to an internal rectifier.
9. FISCO concept applies to fieldbus / circuit only.
10. Entity parameters apply to circuit 2, 3 and 4 and further required to meet the following conditions:
C
o C
i
+ Ccable; Lo Li + Lcable