12 EB 8384-4 EN
Design and principle of operation
Type 3730-4 Positioner (technical data in test certificates additionally apply for explosion-protected devices)
Permissible ambient
temperature
–20 to +80 °C for all versions
–45 to +80 °C with metal cable gland
–25 to +80 °C with inductive limit switch (SJ2-S1N) and metal cable gland
The limits in test certificate additionally apply for explosion-protected devices.
Influ
-
ences
Temperature
≤
0.15 %/10 K
Supply air None
Vibration
≤
0.25 % up to 2000 Hz and 4 g acc. to IEC 770
Electromagnetic
compatibility
Complying with requirements of EN 61000-6-2, EN 61000-6-3, EN 61326-1 and
NAMUR Recommendation NE 21
Explo
-
sion
pro-
tection
ATEX Type 3730-41
Type 3730-48
II 2G Exia IIC T6; II 2D Ex tb IIIC T80°C IP66*
II 3G Ex nA II T6; II 3G Exic IIC T6; II 3D Ex tc IIIC T80°C IP66*
CSA Type 3730-43
Exia IIC T6; Class I, II, Div.1, Groups A, B, C, D, E, F, G;
Ex nA II T6; Ex nL IIC T6; Class I, Div.2, Groups A, B, C, D;
Class II, Div.1, Groups E, F, G
FM Type 3730-43
Class I, Zone 0 AEx ia IIC; Class I, II, III, Div.1, Groups A, B, C, D, E, F, G;
Class I, Div.2, Groups A, B, C, D; Class II, Div.2, Groups F, G
GOST Type 3730-41
Type 3730-38
1Ex ia IIC T6; Ex tb IIIC T80°C Db X, IP66
2Ex nA ic IIC T6/T5/T4 Gc X; Ex tc IIIC T80°C Db X, IP66
IECEx Type 3730-41 Ex ia IIC T6
NEPSI Type 3730-41
Type 3730-48
Ex ia IIC T6
Ex nA II T6; Ex nL IIC T6
CCoE Ex ia IIC T6
INMETRO On request
Electrical connection
One M20 x 1.5 cable gland, for 6 to 12 mm clamping range · Second additional
threaded M20 x 1.5 hole · Screw terminals for 0.2 to 2.5 mm² wire cross-section
Degree of protection IP 66/NEMA 4X
Use in safety-instrumented sys
-
tems (SIL)
Emergency venting at 0 mA set
point and on using the optional
solenoid valve
Observing the requirements of IEC 61508, the systematic capability of the pilot
valve for emergency venting as a component in safety-instrumented systems is
given.
Use is possible on observing the requirements of IEC 61511 and the required
hardware fault tolerance in safety-instrumented systems up to SIL 2 (single de
-
vice/HFT = 0) and SIL 3 (redundant configuration/HFT = 1).
Binary input 1
Input
0 to 30 V DC reverse polarity protection, static destruction limit 40 V,
current consumption 3.5 mA at 24 V, galvanically isolated
Signal Signal “1” at Ue > 5 V · Signal “0” at Ue < 3 V