Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
53
Initialization time exceeded
(Init time >)
The initialization routine lasts too long.
• No pressure on the supply line or there is a leak.
• Supply air failure during initialization.
Status classification
[Maintenance required]
Recommended action
Check attachment and supply pressure.
Re-initialize the positioner.
54
Initialization - solenoid
valve
1) A solenoid valve is installed (Code 45 = YES) and was
not or not properly connected so that an actuator pressure
could not be built up. The alarm is generated when you
attempt to initialize the positioner.
2) If you attempt to initialize the device from the fail-safe
position (SAFE).
Status classification [Maintenance required]
Recommended action Re. 1) Check connection and supply voltage of the forced venting
Code 45 HIGH/LOW
Re. 2) Set the
MAN operating mode over Code 0. Then initialize
the positioner.
55
Transit time too short
(transit time <)
The actuator positioning rates determined during the initializati-
on are so short that the positioner cannot adapt itself optimally.
Status classification
[Maintenance required]
Recommended action
Check the volume restriction setting as described in section 7.2,
re-initialize the positioner.
56
Pin position Initialization was canceled because you are required to enter the
pin position for the selected initialization modes
NOM and SUb.
Status classification
[Maintenance required]
Recommended action
Enter pin position over Code 4 and nominal travel/angle over
Code 5. Re-initialize the positioner.