Table 1 · Technical data
Type 3730-6 Positioner (technical data in test certificates additionally apply for explosion-protected devices)
Travel, adjustable Direct attachment to Type 3277 Actuator: 3.6 to 30 mm
Attachment acc. to IEC 60 534-6-1: 3.6 to 200 mm
Attachment to rotary actuators: 24° to 100° opening angle
Travel range Adjustable Within the initialized travel/opening angle · Can be restricted to maximally 1/5
Reference
variable w
Signal range 4 to 20 mA · Two-wire device with reverse polarity protection · Minimum span 4 mA
Static destruction
limit
30 V
Minimum current 3.6 mA for display · Emergency venting at
£
3.8 mA or
£
4.4 mA depending on version
Load impedance
£
9.2 V (corresponding to 460
W
at 20 mA)
Supply air Supply pressure 1.4 to 7 bar (20 to 105 psi)
Air quality acc. to
ISO 8573-1 (2001)
Max. particle size and density: Class 4 · Oil content: Class 3
Pressure dew point: Class 3 or at least 10 K below the lowest ambient temperature to be expected
Signal pressure (output) 0 bar up to the capacity of supply pressure · Limitable between 1.4 and 7.0 bar by software
Characteristics Adjustable Linear, equal percentage, reverse equal percentage, user-defined (by software)
Butterfly, rotary plug and segmented ball valves: linear/equal percentage
Deviation
£
1 %
Hysteresis
£
0.3 %
Sensitivity
£
0.1 %
Transit time Up to 240 s separately adjustable for exhaust and supply air via software
Direction of action Reversible
Air consumption, steady-state Independent of supply air approx. 110 l
n
/h
Air output
capacity
Actuator pressurized At
D
p = 6 bar: 8.5 m
n
3
/h · At
D
p = 1.4 bar: 3.0 m
n
3
/h · K
Vmax (20 °C)
= 0.09
Actuator vented At
D
p = 6 bar: 14.0 m
n
3
/h · At
D
p = 1.4 bar: 4.5 m
n
3
/h · K
Vmax (20 °C)
= 0.15
Permissible ambient temperature –20 to +80 °C in all versions · –45 to +80 °C with metal cable gland
–25 to +80 °C with inductive limit switch (SJ2-S1N) and metal cable gland
Limits in test certificate also apply for explosion-protected devices.
Influences Temperature
£
0.15 %/10 K
Supply air None
Vibrations
£
0.25 % up to 2000 Hz and 4 g acc. to IEC 770
Electromagnetic compatibility Complying with the requirements of EN 61000-6-2, EN 61000-6-3, EN 61326-1 and NAMUR Recom-
mendation NE 21
Electrical connections
One M20 x 1.5 cable gland for 6 to 12 mm clamping range · Additional second M20 x 1.5 threaded
hole · Screw terminals for 0.2 to 2.5 mm² wire cross-section
Degree of protection IP 66 / NEMA 4X
Use in safety-instrumented systems in
compliance with IEC 61508/SIL
Suitable for use in safety-instrumented systems up to SIL 2
– triggered by the set point,
emergency venting depending on positioner version at
£
3.8 mA or at
£
4.4 mA
– by the optional forced venting, emergency venting at
£
12 V
Suitable for use in safety-instrumented systems up to SIL 3
The current circuit of the set point and the forced venting must both be operated in a
safety-instrumented system
Communication Local SAMSON SSP interface and serial interface adapter
Software requirement (SSP): TROVIS-VIEW with database module 3730-6
HART
®
HART
®
field communication protocol
Impedance in the HART frequency range: receive 350 to 450
W
, send: approx. 155
W
Software requirements (handheld communicator): device description for Type 3730-6
Software requirements (PC): DTM file acc. to Specification 1.2, suitable for integrating the positioner in
frame applications that supports the FDT/DTM concept (e.g. PACTware)
Software re
-
quirements
(HART
®)
Handheld
communicator
Device description for Type 3730-6
PC DTM file acc. to Specification 1.2, suitable for integrating the positioner in frame applications that sup
-
ports the FDT/DTM concept (e.g. PACTware)
Explosion protection
ATEX, IECEx, GOST See summary of explosion protection certificates